After an Rx11 flush the vacuum hangs at 1500–2500 µ and won't reach 500
Almost always it's flush left in puddles in low spots (coil bends, accumulator, line-set traps) plus ruined pump oil. Blank-off test the pump first: won't pull below 100 µ — change the oil. Then warm the low spots to 150 °F on the metal and triple evacuate with 5–10 psi nitrogen. Normal — holds ≤500 µ for 10 minutes (POE). The maker gives no safe residue level — the flush is removed fully with nitrogen and vacuum; you can roughly estimate what stayed with a scale and standing pressure (first item below).
Likely causes, in order
1. Flush left in puddles in low spots (coil bends, accumulator, line-set traps) boils slowly under vacuum and holds the microns, just like water
Tools: Nitrogen with regulator, hoses, catch container, heat gun, micron gauge
- What Rx11 Flush is: an HFC-based solvent (the maker lists a boiling point around 106 °F at atmosphere). Under vacuum it boils easily, but a PUDDLE in a coil bend, in the accumulator or a low loop of the line set evaporates slowly — there's no heat for boiling, the metal cools. Until the puddle boils off, the microns hang at 1500–2500 and barely move. Water behaves exactly the same.
- Sign of residue: with the pump valved off the curve rises fast and LEVELS OFF at one value (the puddle's vapor pressure at its temperature — it can be far above 2500 µ; for water at 72–80 °F it is 20,000–25,000 µ) instead of climbing steadily. Warm a spot — microns jump up and then start falling: you found the puddle.
- Flushing done right: each component SEPARATELY (evaporator, condenser, liquid line, suction line); compressor, TXV/piston, filter drier and accumulator disconnected or bypassed — never flush through them. Inject Rx11 from its own can through the maker's injection valve into a system with NO pressure; NEVER connect the can to nitrogen — it can burst. Then disconnect the can and push the flush through with nitrogen at about 120 psig until clear liquid with no oil or dirt comes out. Catch it in a container, not on the ground.
- The purge afterwards is the key: dry nitrogen through each component until no mist/drops come out. 5–10 minutes per component minimum, a long line set or big condenser — 15. Hold a paper towel at the outlet: dry — done. Purge in the flow direction, bottom-up where possible, to carry puddles out.
- Then: a new filter drier (mandatory — the old one absorbed solvent and water), a suction clean-up drier on a dirty system, micron gauge on the system, evacuate.
- If the microns still hang at 1500–2500: warm the lower coil bends, the accumulator, the low points of the line set with a heat gun (up to 150 °F on the metal) — the solvent boils off in minutes; triple evacuation: pull → nitrogen 5–10 psi for 10 minutes → release → pull, three cycles. Nitrogen “carries out” vapor that won't pull on its own.
- Normal at the end: holds ≤500 µ for 10 minutes (POE) with the pump valved off. The maker gives no “safe” residue level: the flush is removed fully with nitrogen and vacuum. No need to chase 100 µ.
- What happens if some residue stays. The maker only says Rx11 “will not attack components” and that leftover solvent boils off under vacuum; it gives no allowable percentage. Solvent left in the circuit thins the oil (worse compressor lubrication), pressures don't match the chart, subcooling looks “odd”, the TXV may hunt; with moisture present — a risk of acid. Sign of too much: after a weighed-in charge the pressures and SH/SC don't match the chart with no visible cause, oil in the sight glass dark and thin. Fix: recover, new filter drier, nitrogen purge, proper evacuation, recharge by weight. Off-label solvents (brake cleaner, acetone, mineral spirits) — never in a system: they attack seals and leave a residue that won't boil off.
- How to tell HOW MUCH stayed. Exactly — only a lab; in the field, three estimates. 1) Scale during the flush: weigh the Rx11 canister before and after (what went in), weigh the catch container (what came out) — the difference minus what left during the nitrogen purge (usually almost all of it) is the residue; compare with the factory charge in oz. 2) Refrigerant identifier: it samples VAPOR and reads refrigerant purity and air. The flush boils far higher than the refrigerant (106 °F), so little of it is in the vapor — a good reading does NOT prove there is no flush left; a bad one is a reason to recover and recharge. 3) Standing pressure: charge weighed in, unit off and cooled, compare the pressure with the chart at the coldest component's temperature: the solvent boils far higher than the refrigerant (106 °F), so it PULLS the pressure DOWN, air/nitrogen push it up. The maker gives no “psi per percent” figure, and a 1 °F thermometer error on R-410A is already about 3 psi, so standing pressure is only a rough check: clearly below the chart with an exact weight is a reason to recover and redo. Exact — only a lab.
Normal: After the purge and 2–3 rounds the vacuum drops below 500 and holds.
If not: Doesn't drop and doesn't level off → leak; levels off high → more residue/water, heat and purge.
2. Not enough nitrogen purge: after Rx11 purge each circuit until the outlet is dry, 5–10 minutes minimum
3. Vacuum pump oil soaked up flush and moisture — the pump physically can't pull below 1000–1500 µ (blank-off test)
Tools: Fresh vacuum pump oil, micron gauge, cap
- Pump oil is a consumable. It absorbs water and solvent from the system; after an Rx11 flush the very first evacuation kills the oil. Cloudy, milky, smelly — the pump won't go deeper than 1000–1500 µ no matter what you do to the system.
- Blank-off test: disconnect the pump from the system, put the micron gauge right on the pump inlet (or a short core-less hose), run it. A healthy pump with fresh oil: below 100 µ in 1–2 minutes, a good one — 20–50. Won't go below 300–500 → change the oil, repeat. Still no → vanes/seals.
- Change oil on a hot pump: drain, fill, run a minute with the inlet open, drain, fill fresh. After a dirty system — twice. Carry a gallon of oil, not a can.
- Open the gas ballast at the start on a wet system — water passes through the pump as vapor instead of settling in the oil; close it once the gauge reads about 1000–3000 µ (Robinair; NAVAC says 2000 µ) or you won't get depth.
- Hoses: short, 3/8″ or 1/2″, core-less; both ports at once (liquid + suction). A 1/4″ hose with a core makes evacuation 5–10 times longer.
- Micron gauge — only on the system, on the side away from the pump. On the pump it always looks good.
Normal: Blank-off < 100 µ, oil clear.
If not: Oil change (sometimes twice), ballast, hoses.
4. Moisture in the POE and on the walls after an open system — needs a triple evacuation with nitrogen and heat
Tools: Nitrogen, micron gauge, heat gun
- The system sat open (compressor swap, flush) — water on the walls and in the POE oil. POE absorbs moisture from air in 15 minutes and releases it under vacuum for hours.
- Triple evacuation: pull to 1000–1500 µ → nitrogen 5–10 psi, hold 10 minutes (dry nitrogen absorbs vapor) → release to atmosphere → pull; repeat three times. Each round gets deeper.
- Heat: compressor crankcase (a new one too — POE inside), accumulator, receiver, lower coil bends. A warm system releases moisture many times faster. Don't exceed 150 °F.
- Cold outside (below 60 °F): under deep vacuum water freezes and stops evaporating — the microns “stick”. Nitrogen sweeps and heat are mandatory, or pull to 1500, warm, then go deeper.
- Install the new filter drier AFTER the flush and BEFORE the final evacuation, from a sealed package, and charge within an hour of opening it — otherwise it soaks up moisture itself.
- Decay test at the end: ≤500 µ over 10 minutes (POE), flat curve.
Normal: Each round deeper, final holds target.
If not: Levels off high after three rounds → a solvent/water puddle in a low point — heat that spot.
5. Cold (below 60 °F) or a big system/long line set — it simply needs more time
6. Your rig: micron gauge on the pump, hoses with cores, old gaskets
Tools: 1/4″ caps, micron gauge, core tool
- Put the micron gauge on the system (the second service port or a tee at the port), not on the pump: the pump always shows 50 µ, the system shows the truth.
- Hoses: old rubber hoses leak under vacuum by themselves; Schrader cores in the ports and in the hoses are the main source of false rise. Pull the cores with a core removal tool under vacuum or use core-less hoses.
- Rig test: close both manifold valves, cap the hoses, evacuate the manifold with hoses and gauge to 200 µ, valve off the pump — it must hold. It rises → replace gaskets/hoses, don't chase a leak in the unit.
- Ball-valve core removal tools beat a manifold: closed — the system is isolated from pump and hoses, the micron gauge sits on the system.
- Only when the rig holds — draw conclusions about the system.
Normal: Manifold with hoses holds 200–300 µ on its own.
If not: Replace hoses/gaskets/cores, repeat.